24 VDC supply via power rail or connectors
Fast response time
High active output load 725 Ohm / 20 mA
Output line fault detection via status relay
SIL2 certified via Full Assessment according to IEC 61508
9107A is a 1- or 2-channel isolated 1:1 driver.
Operation and drive control of I/P converters, valves and indicators.
Operation of HART® devices is possible as the unit transmits HART® communication signals bi-directionally.
The device can be mounted in and transmit signals to non-classified area and zone 2.
The PR 4511/4501 displays the process value for each channel and can be used to define high and low limits for detection of loop current level. If these limits are exceeded, the status relay will activate.
Dual channel versions can be used for signal splitter applications - 1 in and 2 out.
The PR 4511/4501 detachable display and the green and red front LEDs indicate operation status for each channel.
A tag number can be defined for each channel.
Output line fault detection.
In the 1-channel version the status relay can be used as a simple limit switch.
The devices can be mounted vertically or horizontally without distance between neighbouring units.
High galvanic isolation of 2.6 kVAC.
High accuracy better than 0.1%.
Continuous check of vital stored data for safety reasons.
Environmental Conditions
Specifications range -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II
Mechanical specifications
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 4511 (approx.) 265 g / 350 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6 : 2007
Vibration: 2...13.2 Hz ±1 mm
Vibration: 13.2...100 Hz ±0.7 g
Common specifications
Supply
Supply voltage 19.2...31.2 VDC
Isolation voltage
Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Response time
Response time (0...90%, 100...10%) < 5 ms
Fuse 1.25 A SB / 250 VAC
Max. power consumption ≤ 2 W (2 channels)
Max. internal power dissipation ≤ 2 W (2 channels)
HART bi-directional communication frequency range 0.5...7.5 kHz
Signal / noise ratio > 60 dB
Accuracy Better than 0.1% of selected range
mA, absolute accuracy ≤ ±16 μA
mA, temperature coefficient ≤ ±1.6 μA / °C
Effect of supply voltage change on output (nom. 24 VDC) < ±10 μA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span
Input specifications
Current input
Measurement range 3,5...23 mA
Sensor error detection: Loop break 4...20 mA < 1 mA
Input voltage drop, supplied unit < 2 V @ 23 mA
Input voltage drop, non-supplied unit < 4 V @ 23 mA
Output specifications
Current output
Signal range 3.5...23 mA
Load (max.) 20 mA/725 Ω/14.5 VDC
Load stability ≤0.01% of span / 100 Ω
Current limit ≤ 28 mA
Status relay
Max. voltage 110 VDC / 125 VAC
Max. current 0.3 ADC / 0.5 AAC
Status relay output terminal 33-34: Relay function N.C.
Programmable low setpoint 0...29.9 mA
Programmable high setpoint 0...29.9 mA
Hysteresis for setpoints 0.1 mA
Max. voltage - hazardous installation 32 VDC / 32 VAC
Max. current - hazardous installation 1 ADC / 0.5 AAC
*of span = normal measurement range 4...20 mA
Approvals
EMC 2004/108/EC
LVD 2006/95/EC
UL UL 61010-1
EAC TR-CU 020/2011
DNV Marine Stand. f. Certific. No. 2.4
SIL SIL 2 certified & fully assessed acc. to IEC 61508