Input for RTD, TC and mA
Active / passive mA output
1 or 2 channels
Can be supplied separately or installed on power rail, PR type 9400
SIL 2-certified via Full Assessment
Configuration and monitoring by way of detachable display front (PR 4511/4501); process calibration and signal simulation.
Copying of the configuration from one device to others of the same type via the display front.
TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910, channel 1 / PR 5913, channel 2) for higher accuracy.
The device automatically detects whether it must supply an active or a passive current signal.
Advanced monitoring of internal communication and stored data.
SIL 2 functionality is optional and must be activated in a menu point.
The device can be mounted in and receive signals from non-classified area and zone 2.
Conversion and scaling of temperature (Pt, Ni and TC) and active current signals.
9113A has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
The devices can be mounted vertically or horizontally without distance between neighbouring units.
1 green and 2 red front LEDs indicate operation status and malfunction.
2.6 kVAC galvanic isolation between input, output and supply.
Environmental Conditions
Specifications range -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20...28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & measurement / overvoltage cat. II
Mechanical specifications
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501 / 4511 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 4511 (approx.) 265 g / 350 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13...2.08 mm2 AWG 26...14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6 : 2007
Vibration: 2...13.2 Hz ±1 mm
Vibration: 13.2...100 Hz ±0.7 g
Common specifications
Supply
Supply voltage 19.2...31.2 VDC
Isolation voltage
Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Fuse 400 mA SB / 250 VAC
Max. power consumption ≤ 3.5 W (2 channels)
Communications interface Communication enabler 4511 / Programming front 4501
Signal / noise ratio Min. 60 dB (0...100 kHz)
Average response time incl. delay: Temperature input ≤ 1 s
mA input ≤ 0.4 s
Accuracy Better than 0.1% of selected range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span
Input specifications
RTD input
RTD type Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.) 50 Ω
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in connector 5910 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C
CJC via internally mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temperature-ambient temperature
Sensor error detection Programmable ON or OFF (only wire breakage)
Sensor error current: When detecting / else Nom. 2 μA / 0 μA
Current input
Measurement range 0...20 mA
Programmable measurement ranges 0...20 and 4...20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Programmable ON / OFF
Output specifications
Current output
Signal range 0...20 mA
Programmable signal ranges 0...20 / 4...20 / 20...0 and 20...4 mA
Load (max.) 20 mA/600 Ω/12 VDC
Load stability ≤0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4...20 and 20...4 mA signals 3.8...20.5 mA
Output limitation, on 0...20 and 20...0 mA signals 0...20.5 mA
Current limit ≤ 28 mA
Status relay
Max. voltage 110 VDC / 125 VAC
Max. current 0.3 ADC / 0.5 AAC
Max. AC power 62.5 VA / 32 W
2-wire 4…20 mA output: External 2-wire supply range 3.5...26 VDC
Signal range 4…20 mA
Max. load resistance [Ω] (Vsupply - 3.5) / 0.023 A
Load stability, 4…20 mA output ≤ 0.01% of span / 100 Ω
Effect of external 2-wire supply voltage variation < 0.005% of span / V
*of span = of the currently selected measurement range
Approvals
EMC 2004/108/EC
LVD 2006/95/EC
UL UL 61010-1
EAC TR-CU 020/2011
DNV Marine Stand. f. Certific. No. 2.4
SIL SIL 2 certified & fully assessed acc. to IEC 61508