Brazil
U.S.A
Click to your search
Click to view the menu
Programmable Transmitter; 5116B; PR Electronics;

Programmable Transmitter

Techno Supply  »  Products  »  PR Electronics  »  Programmable Transmitter
Programmable Transmitter
Manufacturer
Programmable Transmitter
Key features

Input for RTD, TC, mV, Ohm, potentiometer, mA and V
2-wire supply > 16.5 V to Ex zone 0
Bipolar voltage input
Output for current, voltage and 2 relays
Universal supply by AC or DC

OVERVIEW

Linearized, electronic temperature measurement with RTD or TC sensor.
Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
Power supply and signal isolator for 2-wire transmitters.
Process control with 2 potential-free relay contacts which can be configured for advanced functions.
Galvanic separation of analog signals and measurement of floating signals.

Mounted vertically or horizontally on a DIN rail. As the devices can be mounted without any distance between neighboring units, up to 42 devices can be mounted per meter.

TECHNICAL DETAILS

Within a few seconds the user can program PR5116B to suit the specific application.

By way of the front push-button the input can be calibrated to the exact span of the process. Zero drift on the process signal can be adjusted by a single press of the front buttton.

A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.

Continuous check of vital stored data for safety reasons.

3-port 3.75 kVAC galvanic isolation.

 

Environmental Conditions

Specifications range -20°C to +60°C

Calibration temperature 20...28°C

Relative humidity < 95% RH (non-cond.)

Protection degree IP20

 

Mechanical specifications

Dimensions (HxWxD) 109 x 23.5 x 130 mm

Weight approx. 235 g

Wire size 1 x 2.5 mm2 stranded wire

Screw terminal torque 0.5 Nm

Vibration IEC 60068-2-6 : 2007

Vibration: 2...25 Hz ±1.6 mm

Vibration: 25...100 Hz ±4 g

 

Common specifications

Supply

Supply voltage, universal 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC

 

Isolation voltage

Isolation voltage, test / working 3.75 kVAC / 250 VAC

 

Response time

Temperature input, programmable (0...90%, 100...10%) 400 ms...60 s

mA / V input (programmable) 250 ms...60 s

 

Auxiliary supplies

2-wire supply (pin 54...52) 28...16.5 VDC / 0...20 mA

Fuse 400 mA SB / 250 VAC

Max. power consumption ≤ 3 W

Communications interface Loop Link

Signal / noise ratio Min. 60 dB (0...100 kHz)

Accuracy Better than 0.05% of selected range

Signal dynamics, input 22 bit

Signal dynamics, output 16 bit

Auxiliary voltages: Reference voltage 2.5 VDC ±0.5% / 15 mA

EMC immunity influence < ±0.5% of span

Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1% of span

 

Input specifications

Common input specifications

Max. offset 50% of selected max. value

RTD input

RTD type Pt100, Ni100, lin. R

Cable resistance per wire (max.) 10 Ω (max. 50 Ω)

Sensor current Nom. 0.2 mA

Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω

Sensor error detection Yes

TC input

Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR

Cold junction compensation (CJC) < ±1.0°C

Sensor error current Nom. 30 μA

Sensor error detection Yes

Current input

Measurement range 0...100 mA

Min. measurement range (span) 4 mA

Input resistance: Supplied unit Nom. 10 Ω + PTC 10 Ω

Input resistance: Non-supplied unit RSHUNT = ∞, VDROP < 6 V

Sensor error detection Loop break 4...20 mA

Voltage input

Measurement range 0...250 VDC -2500...+2500 mV

Min. measurement range (span) 5 mV

Input resistance Nom. 10 MΩ (≤ 2.5 VDC) Nom. 5 MΩ (> 2.5 VDC)

> 5 MΩ (mV input)

Potentiometer via 2.5 V ref. 170 Ω

 

Output specifications

Current output

Signal range 0...20 mA

Min. signal range 10 mA

Load (max.) 20 mA/600 Ω/12 VDC

Load stability ≤0.01% of span / 100 Ω

Current limit ≤ 28 mA

Sensor error indication Programmable 0...23 mA

NAMUR NE 43 Upscale/Downscale 23 mA / 3.5 mA

Voltage output

Signal range 0...10 VDC

Min. signal range 500 mV

Load (min.) 500 kΩ

Relay output

Relay functions Increasing / decreasing Window

Max. voltage 250 VRMS

Max. current 2 AAC

Max. AC power 500 VA

Max. load at 24 VDC 1 A

Sensor error reaction Break / Make / Hold / None

2-wire 4...20 mA output: Signal range 4...20 mA

Load stability, 4…20 mA output ≤ 0.01% of span / 100 Ω

Max. external 2-wire supply 29 VDC

Effect of external 2-wire supply voltage variation < 0.005% of span / V

*of span = of the currently selected measurement range

 

Approvals

EMC 2004/108/EC

LVD 2006/95/EC

PELV/SELV IEC 364-4-41 and EN 60742

ATEX 94/9/EC KEMA 04ATEX1316 X

FM 3023092

UL UL 508

EAC TR-CU 020/2011

EAC Ex TR-CU 012/2011 RU C-DK.GB08.V.00410

DNV Marine Stand. f. Certific. No. 2.4

DOCUMENTS
Related products
 2-Wire Programmable Transmitter
2-Wire Programmable Transmitter
6334B
PR Electronics
2-Wire Transmitter Isolator
2-Wire Transmitter Isolator
3186
PR Electronics
Programmable f/I-f/f Converter
Programmable f/I-f/f Converter
5223B
PR Electronics
CONTACT
19. 3403 2300
Av. Santo Estevão, 509
Vila Rezende - 13405-249

Piracicaba, SP - Brazil
Techno Supply Import and Export Ltda.